Notice the internal fault on the top row of breakers and faulty
cable connection at the bottom of the circuit breaker.
Single
phase circuit breaker
This is an internal fault in the circuit breaker. Early identification
will avoid trip outs from unknown causes. Detection of this
fault prevented futher trip outs, thereby ensuring maximum effecientcies
This
is a faulty connection top of the circuit breaker on the white
phase
Possible
causes are: pinched insulation, stripped terminal screws, damaged
screw heads, damaged cable strands or oxidation
CB's
viewed with covers in place
With this
example you can see clearly that there is a problem developing
at the bottom of the CB. The cover will need to be removed to
identify the nature and cause of the fault